Pengatur Tegangan Keluaran Generator Induksi Akibat Perubahan Beban dan Penurunan Debit Pada Pembangkit Listrik Tenaga Mikrohidro


PENGATUR TEGANGAN KELUARAN GENERATOR INDUKSI
AKIBAT PERUBAHAN BEBAN DAN PENURUNAN DEBIT PADA PLTMH



INTISARI



Kendala umum yang terjadi pada PLTMH ialah kurangnya debit air, apalagi
saat musim kemarau sehingga PLTMH cenderung untuk dinonaktifkan karena tenaga
yang dihasilkan sangat kecil. Generator yang dipakai biasanya generator induksi
dengan konstruksi yang lebih sederhana, kokoh, serta lebih murah perawatannya
dibanding generator sinkron dan generator arus searah. Generator induksi memiliki
regulasi yang jelek, pada kecepatan konstan tegangannya akan turun seiring
bertambahnya beban.
Dalam penelitian ini dikembangkan pengaturan berlapis yaitu mengalihkan
kelebihan tenaga listrik ke ballast load saat debit maksimum dan melepaskan
sebagian beban konsumen saat debit menurun.
Dengan kisaran daya 900 –3300 watt , pengaturan berlapis menghasilkan rata
rata tegangan 209,12 volt dan regulasi 6.36 %. Nilai tegangan ini masih berada pada
kisaran yang ditetapkan yaitu -10%,+5% dari 220 volt. Karenanya pengaturan
berlapis dapat digunakan untuk menjaga kestabilan tegangan saat debit menurun.


Kata kunci : Pengaturan berlapis, debit menurun, ballast load, stabilitas tegangan






















xi









An Induction Generator Output Voltage Regulator in Load Fluctuation
And Flow Rate Decrease at Microhydro Power Plant


Abstract


The common problem at microhydro power plant is low flow rate especially
in the dry season, which can cause the microhydro power plant inoperative. Induction
generator is commonly used for microhydro scheme due to simple, rugged , and low
maintenance cost compared with synchronous or direct current generator. The
induction generator has poor voltage regulation, when it runs at constant speed, its
output voltage drops rapidly with increasing load.
In this research a double controller was developed by balancing input and
output power. It manages the excess power produced at maximum flow rate by
diverting through ballast load and through partial load shading when flow rate
decreases.
With load range 900 – 3300 watt, the double controller produces average
output voltage about 209.12 volt and average voltage regulation about 6.36 %. This
voltage value is still within standard voltage at -10%, +5% from 220 volt. So the
double control strategy can be used to maintain stability of voltage at decreasing flow
rate condition.

Key word : Double control, Decreasing flow rate condition , ballast load, voltage
stability